12 | Commissioning
Installer reference guide
190
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
Heating (if applicable)
Cooling
To perform an operation test run
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Room and Space heating/cooling operation.
1 Set the user permission level to Installer. See "To change
the user permission level"[4106].
2 Go to [A.1]: Commissioning > Operation test run.
3 Select a test from the list. Example: Heating.
4 Select OK to confirm.
Result: The test run starts. It stops automatically when ready
(±30min).
To stop the test run manually:
1 In the menu, go to Stop test run.
2 Select OK to confirm.
INFORMATION
If the outdoor temperature is outside the range of operation, the unit may NOT
operate or may NOT deliver the required capacity.
To monitor leaving water temperature
During test run, the correct operation of the unit can be checked by monitoring its
leaving water temperature (heating/cooling mode).
To monitor the temperature:
1 In the menu, go to Sensors.
2 Select the temperature information.
12.4.4 Actuator test run
Purpose
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select Pump, a test run of the pump will start.
To perform an actuator test run
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Room and Space heating/cooling operation.
1 Set the user permission level to Installer. See "To change the
user permission level"[4106].
2 Go to [A.2]: Commissioning > Actuator test run.
3 Select a test from the list. Example: Pump.