3 Fix the cable with cable ties to the cable tie mountings.
9.2.11 To connect the safety thermostat (normally closed contact)
Wires: 2×0.75mm²
Maximum length: 50m
Safety thermostat contact: 16VDC detection (voltage supplied by PCB).
The voltage-free contact shall ensure the minimum applicable load of
15VDC, 10mA.
—
1 Open the service cover. See "To open the outdoor unit"[461].
2 Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.
a Remove jumper
3 Fix the cable with cable ties to the cable tie mountings.