16 | Disposal
Installer reference guide
208
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
16 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
In this chapter
16.1 To recover refrigerant ............................................................................................................................................................ 208
16.1.1 To open the stop valves ......................................................................................................................................... 209
16.1.2 To manually open the electronic expansion valves............................................................................................... 209
16.1.3 Recovery mode — In case of 3N~ models (7-segments display) .......................................................................... 210
16.1.4 Recovery mode — In case of 1N~ models (7-LEDs display) .................................................................................. 213
16.1 To recover refrigerant
When disposing of the outdoor unit, you need to recover its refrigerant.
To ensure that no refrigerant remains trapped in the unit:
Make sure the stop valves are open (a, b).
Make sure the electronic expansion valves (Y1E, Y3E) are open.
Use all 3 service ports (a, b, c) to recover refrigerant.
Components
Y3E
Y1E
a
b
c
a Liquid stop valve with service port
b Gas stop valve with service port
c Service port 5/16" flare
Y1E Electronic expansion valve (main)
Y3E Electronic expansion valve (injection)
To recover refrigerant when power is OFF
1 Make sure the stop valves are open.
2 Manually open the electronic expansion valves.
3 Recover refrigerant from the 3 service ports.
To recover refrigerant when power is ON
1 Make sure the unit is not running.
2 Make sure the stop valves are open.