Breadcrumb Field code Setting name Range, step
Default value
Date Value
Room
└─ Antifrost
1.4.1 [2-06] R/W 0: Disabled
1: Enabled
1.4.2 [2-05] R/W 4~16°C, step: 1°C
8°C
└─ Setpoint range
1.5.1 [3-07] R/W 12~18°C, step: 1°C
12°C
1.5.2 [3-06] R/W 18~30°C, step: 1°C
30°C
1.5.3 [3-09] R/W 15~25°C, step: 1°C
15°C
1.5.4 [3-08] R/W 25~35°C, step: 1°C
35°C
Room
1.6 [2-09] R/W -5~5°C, step: 0,5°C
0°C
1.7 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
└─ Room comfort setpoint
1.9.1 [9-0A] R/W [3-07][3-06]°C, step: 0,5°C
23°C
1.9.2 [9-0B] R/W [3-09][3-08]°C, step: 0,5°C
23°C
Main zone
2.4 0: Fixed
1: WD heating, fixed cooling
2: Weather de
p
endent
└─ Heating WD curve
2.5 [1-00] R/W -40~5°C, step: 1°C
-10°C
2.5 [1-01] R/W 10~25°C, step: 1°C
15°C
2.5 [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
2.5 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
└─ Cooling WD curve
2.6 [1-06] R/W 10~25°C, step: 1°C
20°C
2.6 [1-07] R/W
25~43°C, step: 1°C
35°C
2.6 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C
2.6 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
18°C
Main zone
2.7 [2-0C] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
2.8.1 [9-01] R/W 15~37°C, step: 1°C
25°C
2.8.2 [9-00] R/W [2-0C]=2:
37~60, step: 1°C
60°C
[2-0C]2:
37~55, step: 1°C
55°C
2.8.3 [9-03] R/W 5~18°C, step: 1°C
7°C
2.8.4 [9-02] R/W 18~22°C, step: 1°C
22°C
Main zone
2.9 [C-07] R/W
0: LWT control
1: Ext RT control
2: RT control
2.A [C-05] R/W 0: -
1: 1 contact
2: 2 contacts
└─ Delta T
2.B.1 [1-0B] R/W [2-0C] 2 (Radiator)
3~10°C, step: 1°C
5°C
[2-0C] = 2 (Radiator)
8°C
2.B.2 [1-0D] R/W 3~10°C, step: 1°C
5°C
└─ Modulation
2.C.1 [8-05] R/W
0: No
1: Yes
2.C.2 [8-06] R/W 0~10°C, step: 1°C
5°C
Additional zone
3.4 0: Fixed
1: WD heating, fixed cooling
2: Weather de
p
endent
└─ Heating WD curve
3.5 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
3.5 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
55°C
3.5 [0-02] R/W 10~25°C, step: 1°C
15°C
3.5 [0-03] R/W -40~5°C, step: 1°C
-10°C
└─ Cooling WD curve
3.6 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
18°C
3.6 [0-05] R/W [9-07]~[9-08]°C, step: 1°C
22°C
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Setpoint mode
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Control
Thermostat type
Delta T heating
Delta T cooling
Modulation
Max modulation
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Cooling minimum
Cooling maximum
Room sensor offset
Room sensor offset
Setpoint mode
Low ambient temp. for LWT main zone heating WD curve.
Heating comfort setpoint
Cooling comfort setpoint
Field settings table
Installer setting at variance with
default value
Room frost protection
Room antifrost temperature
Heating minimum
Heating maximum
4P627274-1 - 2020.09 (#) Setting is not applicable for this unit.