6 | Application guidelines
Installer reference guide
31
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
Fan coil units
Setup
A
B
a
b
A Main leaving water temperature zone
B One single room
a User interface (delivered as accessory)
b Remote controller of the fan coil units
For more information about connecting the electrical wiring to the unit, see
"9.2Connections to the outdoor unit"[478].
The fan coil units are directly connected to the outdoor unit or to the external
backup heater kit, if there is one.
The desired room temperature is set via the remote controller of the fan coil
units.
The space heating/cooling demand signal is sent to one digital input on the
outdoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the fan coil units by one digital output on
the outdoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple fancoil units, make sure each one receives the infrared signal
from the remote controller of the fancoil units.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat or fan coil
unit can only send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Benefits
Cooling. The fan coil unit offers, besides heating capacity, also excellent cooling
capacity.
Efficiency. Optimal energy efficiency because of the interlink function.