EasyManua.ls Logo

Daikin FAA100BUV1B - 8 Operation; Operation Range

Daikin FAA100BUV1B
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 | Operation
Installer and user reference guide
29
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
8 Operation
8.1 Operation range
Use the system in the following temperature and humidity ranges for safe and
effective operation.
For combination with R410A outdoor unit, refer to the following table:
Outdoor units Cooling Heating
RZQ200 Outdoor
temperature
–5~46°C DB –15~15°C WB
Indoor
temperature
14~28°C WB 10~27°C DB
RZQG71~140 Outdoor
temperature
–15~50°C DB –20~15.5°C WB
Indoor
temperature
12~28°C WB 10~27°C DB
RZQSG71~140 Outdoor
temperature
–15~46°C DB –15~15.5°C WB
Indoor
temperature
14~28°C WB 10~27°C DB
Indoor humidity ≤80%
(a)
(a)
To avoid condensation and water dripping out of the unit. If the temperature or the
humidity is beyond these conditions, safety devices may be put in action and the air
conditioner may not operate.
For combination with R32 outdoor unit, refer to the following table:
Outdoor units Cooling Heating
RZAG71~140 Outdoor
temperature
–20~52°C DB –20~24°C DB
–20~18°C WB
Indoor
temperature
17~38°C DB
12~28°C WB
10~27°C DB
RZASG71~140 Outdoor
temperature
–15~46°C DB –15~21°C DB
–15~15.5°C WB
Indoor
temperature
20~38°C DB
14~28°C WB
10~27°C DB
AZAS71+100 Outdoor
temperature
–5~46°C DB –15~21°C DB
–15~15.5°C WB
Indoor
temperature
20~38°C DB
14~28°C WB
10~27°C DB
RZA200+250 Outdoor
temperature
-20~46°C DB -20~15°C WB
Indoor
temperature
14~28°C WB 10~27°C DB