Service Menus
Timer Settings Menu
The Timer Settings Menu is also available from the
Commission Unit Menu, and is described on page 33
Save/Restore Menu
The Save/Restore menu can be used to save or restore the
user congured parameters as well as reset the controller back
to the factory default parameters.
Table 37: Save/Restore Menu
Item Display Name Default Setting Range Password Level
Save Params= No No/Yes 2
Rstr Params= No No/Yes 2
Rstr Factory= No No/Yes 2
SaveToCard= No No/Yes 2
LoadFromCard No No/Yes 2
Save Params is an adjustable item used to save the current
parameters and conguration.
Rstr Params is an adjustable item used to restore the current
parameters and conguration.
Rstr Factory is an adjustable item used to restore the factory
parameters and conguration.
SaveToCard is an adjustable item used to save the current
parameters and conguration to an SD card.
LoadFromCard is an adjustable item used to restore the
current parameters and conguration from an SD card.
NOTE: The controller will automatically perform a reset when
the value of Load From Card is changed from No to
Yes and the enter button is pushed.
Active Alarms Menu
All active alarms as well as the date and time that they were
detected are displayed on the Active Alarm menu. These
alarms are displayed in order of group priority: Faults rst,
Problems second, and Warnings last. Within each group,
alarms are displayed in the order that they were detected.
Table 38: Active Alarm Menu
Item Display Name Default Setting Range Password Level
Active Alm Count= 0–10 None
ClrAlms= No
No
ClrFlts
ClrPrblms
ClrWrngs
ClrAllAlms
None
+Alarm 1:Alarm Type None
+Alarm 2:Alarm Type None
Event Log Menu
The last fty events (such as variable compressor unloading
events, both detection and return to normal) as well as the
date and times that they were detected are displayed on the
Event Log menu. These events are displayed in the order
that they were detected. The event that was detected most
recently is displayed rst. Multiple occurrences of the same
event may appear.
OM 920-6 • MICROTECH UNIT CONTROLLER 62 www.DaikinApplied.com
Menu desCrIpTIons

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals