Rooftop Equipment Warranty Registration Form (continued)
13F-4158 (06/17) 5
Select Yes or No. If not applicable to the type of unit, select N/A.
N. Flame failure shutoff (seconds): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
O. Airswitch OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
P. High Gas Pressure Switch OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Q. Low Gas Pressure Switch OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
R. Main Gas Valve Close-off OK?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
S. Modulation Gas Heat Performance
Gas Pressure
Mod. Valve Reg. Valve
25% ______ in Wc. 25% ______ in Wc.
50% ______ in Wc. 50% ______ in Wc.
75% ______ in Wc. 75% ______ in Wc.
100% ______ in Wc. 100% ______ in Wc.
VII. Hot Water Coil
A. Pressure test OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ye s No N/A
VIII. Heat Recovery
A. Heat wheel rotates freely? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . Yes No N/A
B. Heat wheel VFD operates properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ye s No N/A
C. Heat wheel VFD . . . . . . . . . . . . . . Model No. _________________________ Serial No. ___________________________
D. Check for air bypass around heat wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ye s No N/A
IX. Design Flow Calibration
A. Verify power is supplied to the MicroTech III unit controller . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
B. Verify that the shipping screws have been removed from the measuring station vane . . . . . . . . . . . . Yes No N/A
C. Examine station for damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
D. Record Level Position after calibration
• LH Level Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________
• RH Level Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________
NOTE: This is viewed in the MicroTech III controller, in the Min OA setup menu.
WarranTy reGIsTraTIon form
www.DaikinApplied.com 117 IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS