6.4. Installing the unit
/CMGUWTGVJGWPKVKUKPUVCNNGFNGXGNQPCUWHƂEKGPVN[UVTQPIDCUGVQ
prevent vibration and noise.
NOTE
When the installation height of the unit needs to be increased, do not
use stands to only support the corners.
CENTER OF
PRODUCT
A
A
A
A
A
A
CENTER OF
PRODUCT
A
t3-15/16 in. (100 mm)
X Not allowed
O Allowed
The height of the foundation must be at least 5-7/8 in. (150 mm )
HTQOVJGƃQQT
In heavy snowfall areas, this height should be increased, depending
on the installation place and condition.
The unit must be installed on a solid longitudinal foundation (steel
beam frame or concrete) and make sure the base under the unit is
larger than the gray marked area.
3
4
2
5
6
7
1
8
11 11
10 9 10
&KOGPUKQPUHQTCDQXGƂIWTG
1
Hole for foundation
bolt
9/16 in. (15 mm) × 7/8 in. (22.5 mm)
oblong hole: 4 positions
2
Inner dimension of the
base
d25-1/4 in. (641 mm)
3
Distance between
foundation bolt holes
29 in. (729 mm)
4 Width of unit 30-1/8 in. (765 mm)
5
Outer dimension of
the base
t30-1/8 in. (765 mm)
6
Longitudinal foundation
dimension
REYQ72 type: 36-5/8 in. (930 mm)
REYQ96-168 type: 48-13/16 in. (1240 mm)
REYQ192-240 type: 68-7/8 in. (1750 mm)
7
Distance between
foundation bolt holes
REYQ72 type: 30-3/16 in. (766 mm)
REYQ96-168 type: 42-3/8 in. (1076 mm)
REYQ192-240 type:
62-7/16 in. (1586 mm)
8
Distance between
foundation bolt holes
REYQ72 type: 15-1/16 in. (383 mm)
REYQ96-168 type: 21-3/16 in. (538 mm)
REYQ192-240 type: 31-1/4 in. (793 mm)
9*
1
Hole for foundation
bolt
9/16 in. (15 mm) × 7/8 in. (22.5 mm)
oblong hole: 2 positions
10*
1
Hole for foundation
bolt
9/16 in. (15 mm) × 7/8 in. (22.5 mm)
oblong hole: 4 positions
REYQ192-240 type only
11*
1
Distance between
foundation bolt holes
REYQ192-240 type only : 15-5/8 in.
(397 mm)
*1 In areas where compliance with the FL Building Code is required,
ƂZCVCPFYKVJHQWPFCVKQPDQNVU
Fasten the unit in place using 4 foundation bolts
1/2 in. (M12). It is best to screw in the foundation
bolts until their length remains 13/16 in. (20 mm)
above the foundation surface.
A
A=13/16 in. (20 mm)
NOTE
There are restrictions on the refrigerant pipe connecting order
between outdoor units in the case of the multi system.
5GG1WVFQQTWPKVUEQODKPCVKQPUQPRCIG|HQTFGVCKN
9JGPKPUVCNNKPIQPCTQQHOCMGUWTGVJGTQQHƃQQTKUUVTQPIGPQWIJ
and be sure to waterproof all work.
Make sure the area around the machine drains properly by setting
up drainage grooves around the foundation.
Drain water is sometimes discharged from the outdoor unit when it
is running.
For anti-corrosion type, use nuts with resin washers. If the paint on
nut connections comes off, the anti-corrosion effect may decrease.