Troubleshooting for Outdoor Unit SiBE121135_A
209 Service Diagnosis
7.7 OL Activation (Compressor Overload)
Error Code E5
Outdoor Unit LED
Display
A j 1 i 2 h 3 i 4 h 5 h
LED5 is equipped only on the 5-room model.
Method of Error
Detection
A compressor overload is detected through compressor OL.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of discharge pipe thermistor
Defective discharge pipe thermistor
Disconnection of connector [S40]
Disconnection of 2 terminals of OL (Q1L)
Defective OL (Q1L)
Broken OL harness
Defective outdoor electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve