SiBE121135_A Troubleshooting for Outdoor Unit
Service Diagnosis 218
7.14 Position Sensor Abnormality
Error Code H6
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
LED5 is equipped only on the 5-room model.
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Disconnection of the compressor relay cable
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is outside the specified range.