SiBE121135_A Troubleshooting for Outdoor Unit
Service Diagnosis 222
7.16 Thermistor or Related Abnormality (Outdoor Unit)
Error Code H9, J3, J6, J8, J9, P4
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
∗ LED5 is equipped only on the 5-room model.
Method of Error
Detection
This type of error is detected by checking the thermistor input voltage to the microcomputer.
A thermistor error is detected by checking the temperature sensed by each thermistor.
Error Decision
Conditions
The thermistor input is above 4.96 V or below 0.04 V with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
The system is shut down if all the units are judged as the J8 error.
Supposed
Causes
Disconnection of the connector for the thermistor
Defective thermistor corresponding to the error code
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting In case of P4
Replace the outdoor unit PCB.
P4 : Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.