EasyManua.ls Logo

Daikin VAM-FA - Page 73

Daikin VAM-FA
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
1
15
Ventilation • Heat reclaim ventilation
71
Heat reclaim ventilation • VAM-FA/FB
15 Control systems
15 - 3 Basic patterns
15 - 3 - 2 Independent system
Control with two remote controls
Group control
Purpose and functions
For control of one HRV unit (Also one group control is
possible)
Sophisticated operation and indication output are possible
from either local place or remote place by two liquid crystal
remote controls.
Either one of two liquid crystal remote controls can be used
for all operations and indications.
(However, initial setting can only be carried out by the
master remote control)
Point
The wiring to the remote controls must be branched from the
unit as shown in the diagram.
(Though the crossover between the master and slave
remote controls is acceptable, the work to put two wires into
the remote control takes time.)
Example of wiring for control
Note
1. The maximum allowable total length of wires to the remote
control is 500 m.
2. Simple remote controls cannot be used for control with two
remote controls.
The following setting is required
Either one of two remote controls must be set as a slave
remote control.
Required optional accessories
Liquid crystal remote control × 2
BRC301B61
Purpose and functions
Simultaneous control of multiple HRV units (max. 16 units) is
available (for application to such as a spacious room)
All operation and individual setting can be carried out from
one remote control.
In case the liquid crystal indicates malfunction, the indication
of HRV unit No. shows in the display.
(If another remote control is additionally installed, control
with two remote controls is possible.)
Point
No address setting is required because address is
automatically set.
(The address is optionally allocated. The address No. can
be confirmed by setting to service mode “Forced fan
operation” and be checked whether the unit is in operation
or not.)
Example of wiring for control
Note
1. The maximum allowable total length of wires to the remote
control is 500 m.
2. One liquid crystal remote control is always required.
3. Simple remote controls cannot be used for control with two
remote controls.
The following setting is required
No setting is required. (product is to be just as it was when
shipped from the factory)
Required optional accessories
One set of liquid crystal remote control
BRC301B61
X9A
X10A
X11A
J1 J2 F1 F2
P1P2
P1P2
JC
SS1
Main
P1P2
Sub
(HC0023)
HRV unit
Remote control
for HRV unit
Remote control
for HRV unit
X9A
X10A
X11A
J1 J2 F1 F2
P1P2
P1P2
JC
SS1
X9A
X10A
X11A
J1 J2 F1 F2
P1P2
JC
SS1
X9A
X10A
X11A
J1 J2 F1 F2
P1P2
JC
SS1
(HC0024)
HRV unit
Remote control
for HRV unit
HRV unit HRV unit

Related product manuals