Test Operation Si39-303
96 General Information
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
(V3081)
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)
Demand level 1 instructing
Power consumption set by
"Demand 1 level setting".
Demand level 2 instructing Demand level 3 instructing
The power
consumption during
the demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power consumption"
has been set at
factory.)
(V3082)
The power consumption set with "Demand 1 level setting".
When the
"Continuous demand
setting" is set to ON
("OFF" has been set
at factory.) , the
power consumption
can be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at factory.)
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)
(V3083)
The power consumption set with "Demand 1 level setting".
H
Demand level 2 instructing
H
Demand level 3 instructing
The power
consumption can be
set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at factory.)
H
During continuous demand operation,
when the external demand instruction is
received repeatedly, the instruction with
higher demand level has the precedence.
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)