Si39-303 Test Operation
General Information 85
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
26
Night-time low noise
operation start
setting
8788787
About 20:00
8777778
About 22:00 (factory
8777787
About 24:00
8777877
27
Night-time low noise
operation end setting
8788788
About 6:00
8777778
About 7:00
8777787
About 8:00 (factory setting)
8777877
28
Power transistor
check mode
8788877
OFF
8777778
ON
8777787
29
Capacity
precedence setting
8788878
OFF
8777778
ON
8777787
30 Demand setting 1
8788887
60% demand
8777778
70% demand
8777787
80% demand
8777877
32
Continuous demand
setting
8877777
OFF
8777778
ON
8777787
38
Emergency
operation
(Master unit with
multi-outdoor-unit
system is inhibited to
operate.)
8877887
OFF
8777778
Master unit operation: Inhibited
8777787
39
Emergency
operation
(Slave unit 1 with
multi-outdoor-unit
system is inhibited to
operate.)
8877888
OFF
8777778
Slave unit 1 operation: Inhibited
8777787
40
Emergency
operation
(Slave unit 2 with
multi-outdoor-unit
system is inhibited to
operate.)
8878777
OFF
8777778
Slave unit 2 operation: Inhibited
8777787