Test Operation Si39-303
86 General Information
c. Monitor mode
Setting item 0 Display contents of “Number of units for sequential start,
and others”
No. Setting item
LED display
Data display
H1PH2PH3PH4PH5PH6PH7P
0
Number of units for sequential
starting, and others
9777777
See below
1 C/H unified address
9777778
Lower 6 digits
2 Low noise/demand address
9777787
3 Not used
9777788
4 Airnet address
9777877
5 Number of connected indoor units
9777878
6 Number of connected BS units
9777887
7
Number of connected zone units
(excluding outdoor and BS unit)
9777888
8 Number of outdoor units
9778777
9 Number of connected BS units
9778778
Lower 4 digits:
upper
10 Number of connected BS units
9778787
Lower 4 digits:
lower
11
Number of zone units (excluding
outdoor and BS unit)
9778788
Lower 6 digits
12 Number of terminal blocks
9778877
Lower 4 digits:
upper
13 Number of terminal blocks
9778878
Lower 4 digits:
lower
Number of units for sequential
start
1 unit
9777777
2 units
9797777
3 units
9787777
EMG operation /backup
operation setting
ON
9778777
OFF
9777777
Defrost select setting Short
9777877
Medium
9777977
Long
9777777
Te setting H
9777787
M
9777797
L
9777777
Tc setting H
9777778
M
9777779
L
9777777
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE button (BS1) when in
“Setting mode 1”.
Push the SET button (BS2) and set
the LED display to a setting item.
Push the RETURN button (BS3) to
display different data of set items.
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
Push the MODE button (BS1) and
returns to “Setting mode 1”.
(V2765)