Accessories ED34-862
140 FXCQ-M
Filter Chamber
Specifications
Precaution at use
1. The filter chamber will be needed when the high efficiency filter will be built in. But, it is impossible to build in more
than two kinds filter at the same time.
Installation
High Efficiency Filter (Filter chamber is required for the high efficiency filter)
Specifications
Note:
1. ∗ The life time at the dust density 0.15 mg/m³.
2. Replace the fan motor's capacitor in accordance with the guide in next page, when the high efficiency filter is
used.
Model
Item
KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160
External
Dimensions (mm)
H 50 50 50 50
W 780 995 1180 1670
D 600 600 600 600
Applicable Models 20 · 25 · 32 Class 40 · 50 Class 63 Class 80 · 125 Class
Model
Item
KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160
External Dimensions
(H×W×D)(mm)
(30×460×145)
×2
(30×675×145)
×2
(30×860×145)
×2
(30×660×145)
×4
(30×460×145)
×2
(30×675×145)
×2
(30×860×145)
×2
(30×660×145)
×4
Dust Collection
Efficiency (%)
65% (Colorimetric method) 90% (Colorimetric method)
Initial Pressure Loss
(Pa)
29 39 39 49
Final Pressure Loss
(Pa)
78 78
Filter Non-woven fabric of synthetic fiber Non-woven fabric of synthetic fiber
Life Time (h) ∗ 2500 hours 2500 hours 2100 hours 2000 hours
Applicable Models
20 · 25 · 32
Class
40 · 50
Class
63
Class
80 · 125
Class
20 · 25 · 32
Class
40 · 50
Class
63
Class
80 · 125
Class