ED34-862 Installation
FXUQ-MA 403
12
Bolt Pitch
(2) Open the eyebolt holes or the holes for passing the piping and wiring out of the unit.
• Set the locations for the above holes, open them up and then lay the piping (refrigerant) and wiring
(including both power supply and transmission wiring) up to the piping and wiring connections in the unit.
• It might be necessary to reinforce the ceiling frame to maintain the levelness and to prevent vibration.
Consult an architect or carpenter for details.
(3) Install the hanging bolts. (Use M8 hanging bolts.)
• If it is pre-set, use hole-in anchors. Otherwise, use embedded inserts or embedded foundation bolts to
make sure that the weight of the unit can be supported. Adjust the distance to the ceiling beforehand.
255
(Suspension bolt pitch)
(Suspension bolt pitch)
Fig. 3
When hanging the unit from the ceiling
(1) Check the relative locations of ceiling hole, unit, and hanging bolts.
(length: mm)
Ceiling slab
Long nut or
turnbuckle
Suspension bolt
BEV unit proper
Note: All the above parts are field supplied.
<Example of installation>
Anchor
Fig. 4
37 182
287
Fig. 5
When installing the unit on a wall
(1) Check the relative locations of ceiling hole, unit, and hanging bolts.
(length: mm)
Nut (field supplied)
Washer
(field supplied)
10-15mm
Hanging fitting
BEV main unit
Hanging bolt
(field supplied)
Fig. 6
When hanging the unit from the ceiling
(1) Temporarily install the BEV unit.
(2) Adjust the height of the main unit with the nut.
(3) Check that the main unit is installed on the level.
(4) Tighten the nut on both the top and the bottom
to fix securely.
Use only accessories and parts which are of the designated specification when installing.
Mount the hanging fittings to
hanging bolts. Secure the hanging fittings on
the top and the bottom with nuts (M8, field
supplied) and washers (M8: Outside diameter
size 24 to 28 mm) (field supplied).
Mounting screws
(field supplied)
Hanging fitting
BEV unit
When installing the unit on a wall
(1) Mount the hanging fittings with the
mounting screws (4 pieces).
(2) Use M4 screws.
Fig. 7