EasyManua.ls Logo

Daitsu DS-9KIDR - 4-Way Value Reversing Abnormal

Daitsu DS-9KIDR
89 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Air Conditioner Service Manual
58
3.2.19 F8---4-Way Value Reversing abnormal
On heating mode, if IDU Coil temperature tested lower than Room temperature 5 or even more after compressor
works for 8min, unit will show F8 code.
Display F8
Is there 220V
voltage on the 4-
way valve?
Replace ODU PCB
Multimeter test the
valve coil resistance,
does it open or short
circuit?
Replace 4-way valve coil
End
the 4-way valve
wiring connection
correct?
Re-connect
F8 disappear?
F8 disappear?
Yes
No
Yes
Yes
Yes
Yes
No
No
No
No

Table of Contents

Related product manuals