9.2.20 Fy--- Gas leakage protection
After compressor works in high frequency for 9 min, if the temperature on IDU evaporator & ODU condenser has
only a little variation comparing previous, but, the compressor discharge temperature on high level, then the unit will
show Fy failure code.
Check the pipe
connection, any gas
leakage?
Repair and charge
new gas as SPEC.
Check the room &
evaporator coil
temperature.
Is the temperature
difference more than
2℃ btw RT & IPT after
unit start 10min.?
The sensor well
connect to PCB?
Any of the evaporator
pipe blocked
Is malfunction
eliminated?
the sensor open
or short circuit?