EasyManuals Logo

Danfoss 087H3241 User Guide, Installation & Maintenance

Danfoss 087H3241
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
24 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK
DH-SMT/DK VI.KT.G2.02 © Danfoss 05/2007 25
Total stop 5021
Setting range Factory setting
ON / OFF OFF
Decide whether you want a total stop during the setback temperature period.
ON: The desired system temperature is lowered to ‘Standby T’ (line 7093).
‘Temp. min.’ (line 2177) is overruled.
Desired system temp. °C
‘Standby T
Time
OFF: No total stop
Desired system temp. °C
‘Standby T
Time
S1 T filter (outdoor temp. filter) 5081
Setting range Factory setting
1 ... 200 100
Dampens the measured outdoor temperatures by the set factor.
1: Fast (low filter constant)
200: Slow (high filter constant)
Cut-out (limit for heating cut-out) 5179
Setting range Factory setting
OFF / 1 ... 50 °C 18 °C
Set the outdoor temperature limit at which you want the heating system to stop. The
valve closes and after about 3 min. the heating circulation pump stops. ‘Temp. min.
set in line 2177 will be ignored.
Temp. Actual outdoor temp. Accumulated outdoor temp.
18 °C
Time
Heating Heating OFF Heating
This function can save energy by stopping the heating system when the outdoor
temperature gets above a set limit. The heating system switches ON again when the
outdoor temperature and the accumulated outdoor temperature become lower than
the set limit.
The heating cut-out is only active when the controller mode is AUTO (scheduled operation).
When the limit value is set to OFF, there is no heating cut-out.

Other manuals for Danfoss 087H3241

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 087H3241 and is the answer not in the manual?

Danfoss 087H3241 Specifications

General IconGeneral
BrandDanfoss
Model087H3241
CategoryController
LanguageEnglish

Related product manuals