[1665] Analog Output 42 [mA]
[1666] Digital Output [bin]
[1690] Alarm Word
[1692] Warning Word
[1694] Ext. Status Word
15-11 Logging Interval
Range: Function:
Application
Depend-
ent*
[0 - 0 N/A] Enter the interval in milliseconds between each sampling of the variables to be logged.
15-12 Trigger Event
Option: Function:
Selects the trigger event. When the trigger event occurs, a window is applied to freeze the log. The
log will then retain a specified percentage of samples before the occurrence of the trigger event
(par.15-14
Samples Before Trigger
).
[0] * False
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current limit
[7] Out of current range
[8] Below I low
[9] Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[33] Digital input DI18
[34] Digital input DI19
3 Parameter Description ADAP-KOOL
®
Drive Programming Guide
128
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3