None of the two functions are active if
Hand On
or
Off
modes have been activated via the LCP. If selecting
Hand On
or
Off
, the two timers will be reset
to 0, and not start counting until
Auto
is pressed and an active start command applied.
NB!
A Coast command or missing Run Permissive signal will override both Minimum Run Time and Interval Between Starts functions.
22-75 Short Cycle Protection
Option: Function:
[0] Disabled Timer set in
Interval Between Starts
, par. 22-76 is disabled.
[1] Enabled Timer set in
Interval between Starts
, par. 22-76 is enabled.
22-76 Interval Between Starts
Range: Function:
300 s* [0 - 3600 s] Sets the time desired as minimum time between two starts. Any normal start command (Start/Jog/
Freeze) will be disregarded until the timer has expired.
22-77 Minimum Run Time
Range: Function:
0 s* [0 - par. 22-76 s] Sets the time desired as minimum run time after a normal start command (Start/Jog/Freeze). Any
normal stop command will be disregarded until the set time has expired. The timer will start counting
following a normal start command (Start/Jog/Freeze).
The timer will be overridden by a Coast (Inverse) or an External Interlock command.
NB!
Does not work in cascade mode.
3.17.7 22-78 Minimum Run Time Override
22-78 Minimum Run Time Override
Option: Function:
[0] * Disabled
[1] Enabled
3.17.8 22-79 Minimum Run Time Override Value
22-79 Minimum Run Time Override Value
Range: Function:
0.000 Proc-
essCtrlU-
nit*
[-999999.999 - 999999.999 Proc-
essCtrlUnit]
3 Parameter Description ADAP-KOOL
®
Drive Programming Guide
180
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark