23-02 OFF Time
Array [10]
Range: Function:
0 N/A* [0 - 0 N/A] Sets the OFF time for the Timed Action.
NB!
The frequency converter has no back up of the clock function and the set date/
time will reset to default (2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed. In par.0-79
Clock Fault
it is possible
to program for a Warning in case clock has not been set properly, e.g. after a
power down.
23-03 OFF Action
Select the action during OFF Time. See par. 13.52
SL Controller Action
for descriptions of the options.
Array [10]
[0] * DISABLED
[1] No action
[2] Select setup 1
[3] Select setup 2
[4] Select setup 3
[5] Select setup 4
[10] Select preset ref. 0
[11] Select preset ref. 1
[12] Select preset ref. 2
[13] Select preset ref. 3
[14] Select preset ref. 4
[15] Select preset ref. 5
[16] Select preset ref. 6
[17] Select preset ref. 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[26] DC brake
[27] Coast
[28] Freeze output
[29] Start timer 0
[30] Start timer 1
[31] Start timer 2
[32] Set dig. out. A low
[33] Set dig. out. B low
[34] Set dig. out. C low
[35] Set dig. out. D low
[36] Set dig. out. E low
[37] Set dig. out. F low
[38] Set dig. out. A high
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
187