EasyManua.ls Logo

Danfoss ADAP-KOOL Drive - Page 193

Danfoss ADAP-KOOL Drive
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23-51 Period Start
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the Energy Log starts update of the counters. First data will be stored
in counter [00] and start at the time/date programmed in this parameter.
Date format will depend on setting in par.0-71
Date Format
and time format on setting in par.
0-72
Time Format
.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-53 Energy Log
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with a number of elements equal to the number of counters ([00]-[xx] below parameter
number in display). Press OK and Step between elements by means of
and
buttons on the
Local Control Panel.
Array elements:
Data from latest period is stored in the counter with the highest index.
At power down all counter values are stored and resumed at next power up.
NB!
All counters are automatically reset when changing the setting in par.23-50
Energy Log Resolution
. At overflow the update of the
counters will stop at maximum value.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
193
3

Related product manuals