23-64 Timed Period Stop
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the Trend Analyses must stop update of the Timed Bin counters.
Date format will depend on setting in par.0-71
Date Format
, and time format on setting in par.
0-72
Time Format
.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
0 %* [0 - 100. %] Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between
elements by means of
and
buttons on the LCP.
Set the minimum limit for each interval in par.23-61
Continuous Bin Data
and par.23-62
Timed Bin
Data
. Example: if selecting
counter
[1] and changing setting from 10% to 12%,
counter
[0] will be
based on the interval 0 - <12% and
counter
[1] on interval 12% - <20%.
23-66 Reset Continuous Bin Data
Option: Function:
Select
Do reset
[1] to reset all values in par.23-61
Continuous Bin Data
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0] * Do not reset
[1] Do reset
23-67 Reset Timed Bin Data
Option: Function:
Select
Do reset
[1] to reset all counters in par.23-62
Timed Bin Data
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0] * Do not reset
[1] Do reset
3.18.5 23-8* Payback counter
The ADAP-KOOL Drive includes a feature which can give a rough calculation on payback in cases where the frequency converter has been installed in an
existing plant to ensure energy saving by changing from fixed to variable speed control. Reference for the savings is a set value to represent the average
power yielded before the upgrade with variable speed control.
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
197
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ADAP-KOOL Drive and is the answer not in the manual?

Danfoss ADAP-KOOL Drive Specifications

General IconGeneral
BrandDanfoss
ModelADAP-KOOL Drive
CategoryDC Drives
LanguageEnglish

Related product manuals