Staging Speed is calculated with the following formula:
η
STAGE
= η
HIGH
η
STAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
STAGE100%
is the value
of Staging Threshold.
25-46 Destaging Speed [RPM]
Option: Function:
0 N/A Readout of the below calculated value for Destaging Speed. When removing a fixed speed com-
pressor, in order to prevent an undershoot of pressure, the variable speed compressor ramps up to
a higher speed. When the variable speed compressor reaches the “Destaging Speed” the fixed speed
compressor is destaged. Destaging Speed is calculated based on
Destaging Threshold
, par. 25-43,
and
Motor Speed High Limit
, par. 4-13.
Destaging Speed is calculated with the following formula:
η
DESTAGE
= η
HIGH
η
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the
value of Destaging Threshold.
25-47 Destaging Speed [Hz]
Option: Function:
Readout of the below calculated value for Destaging Speed. When removing a fixed speed com-
pressor, in order to prevent an undershoot of pressure, the variable speed compressor ramps up to
a higher speed. When the variable speed compressor reaches the “Destaging Speed” the fixed speed
compressor is destaged. Destaging Speed is calculated based on
Destaging Threshold
, par. 25-43,
and
Motor Speed High Limit [Hz]
, par. 4-14.
Destaging Speed is calculated with the following formula:
η
DESTAGE
= η
HIGH
η
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the value of Destaging Threshold.
3.19.6 25-8* Status
Readout parameters informing about the operating status of the pack controller and the compressors controlled.
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
207