[196] Fire Mode The frequency converter is operating in Fire Mode. See 24-0*
Fire Mode
.
[197] Fire Mode was act. The frequency converter has been operating in Fire Mode, but is now back in normal operation.
[198] Drive Bypass To be used as signal for activating an external electromechanical bypass switching the motor direct
on line. See 24-1*
Drive Bypass
.
If enabling the Drive Bypass Function, the frequency converter is no longer Safety
Certified (for using the Safe Stop in versions where included).
[199] Injection Control Indicates that the digital output is used for providing Injection ON-OFF signal. A low voltage on the
selected digital output indicates Injection OFF, while high voltage indicates Injection ON.
The below setting options are all related to the Cascade Controller.
Wiring diagrams and settings for parameter, see group 25-** for more details.
[200] Full Capacity All pumps running and at full speed
[201] Compressor 1 Running One or more of the compressors controlled by the Cascade Controller are running. The function will
also depend on the setting of in
Fixed Lead Compressor
, par. 25-06. If set to
No
[0] Compressor 1
refers to the compressor controlled by relay RELAY1 etc. If set to
Yes
[1]Compressor 1 refers to the
compressor controlled by the frequency converter only (without any of the build in relays involved)
and Compressor 2 to the compressor controlled by the relay RELAY1. See below table:
[202] Compressor 2 Running See [201]
[203] Compressor 3 Running See [201]
Setting in Par. 5-3*
Setting in Par. 25-06
[0] No [1] Yes
[201] Compressor 1 Running Controlled by RELAY1 Frequency Converter controlled
[202] Compressor 2 Running Controlled by RELAY2 Controlled by RELAY1
[203] Compressor 3 Running Controlled by RELAY3 Controlled by RELAY2
5-30 Terminal 27 Digital Output
Option: Function:
[0] * No operation Functions are described under 5-3*
5-31 Terminal 29 Digital Output
Option: Function:
[0] * No operation Functions are described under 5-3*
5-32 Term X30/6 Digi Out (MCB 101)
Option: Function:
[0] * No operation This parameter is active when option module MCB 101 is mounted in the frequency converter.
Functions are described under 5-3*
5-33 Term X30/7 Digi Out (MCB 101)
Option: Function:
[0] * No operation This parameter is active when option module MCB 101 is mounted in the frequency converter.
Functions are described under 5-3*
3.7.5 5-4* Relays
Parameters for configuring the timing and the output functions for the relays.
5-40 Function Relay
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array parameter.
3 Parameter Description ADAP-KOOL
®
Drive Programming Guide
76
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3