AK-PC 551 Technical brochure RC8CF102 © Danfoss 08-2014 13
Example: Wizard
Condenser
Set the condenser control as well as control
sensor and reference settings� The pressure
range of the pressure transmitter can be
set�
Pc sensor max� range: 34.0 bar
Pc sensor min� range: -1.0 bar
Reference mode: Floating
Setpoint: 30 °C
Min� reference: 15 °C
Max� reference: 45 °C
Capacity ctrl� mode: Speed
No� of fans: 1
VSD Start via DO: Yes
Monitor fan safety: Common
Extra
Select whether to use an alarm relay and
Modbus network address�
Alarm output: No relay
Modbus address: 100
Summary
Get an overview of the inputs and outputs
generated by the wizard�
Next step
Select which main menu to go to� Press
DOWN to go to the selected menu�
It is recommended to check the IO (input /
output) conguration before starting the
controller�
Apply wizard settings
Press ENTER to apply the wizard settings
to the controller including automatic
assignment requested inputs and outputs�
Press DOWN to go to the selected menu and nish the
wizard