EasyManua.ls Logo

Danfoss AK-PC 551

Danfoss AK-PC 551
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 Technical brochure RC8CF102 © Danfoss 08-2014 AK-PC 551
Network setup
AK-PC 551 can be integrated into a Modbus communication
network� It is important that the installation of the communication
cable is done correctly� Also remember correct termination at
both ends of the cable�
Please refer to separate literature no� RC8AC
When AK-PC 551 is integrated into an ADAP-KOOL® network
with a system manager of the types AK-SC 355 or AK-SM 850 it is
important that some settings are set correctly
1. Set unit of setpoints
Go to Main menu -> Plant type
The "Unit of setpoints" has to be set up before the controller is
scanned on the network� This is required in order for the front
end (AK-SC 355 or AK-SM 850) to present settings/readings in the
correct units (saturated temperature or pressure)�
2. Set network address
Go to Main menu -> System -> Network
3. Set the Modbus address in the range 1-199
- assuring that the selected address is not occupied by another
controller on the network�
4. Make sure that the Baud rate of the controller is set to “384”
(38400 bits per second)
5. Make sure that the serial mode is set “8E1”
When a network scan is carried out the controller will be identied
as:
"AK-PC 551 - xxxx (MC250000)" - if the control setup unit is
saturated temperature�
"AK-PC 551 - xxxx (MC250001)" - if the control setup unit is
pressure
You can check the scanned controller in the front end in the menu
entry:
Conguration -> Network Nodes -> Scan Status
Network
Modbus address and
Baudrate
Scanned controllers shown in the front end
The AK-SM 850/AK-SC 355 must have software version G03�090 or
higher in order to support AK-PC 551� The software version can be
found in menu entry:
Info -> Information -> SW version
Unit of setpoints

Other manuals for Danfoss AK-PC 551

Related product manuals