EasyManuals Logo

Danfoss AK-PC 551 Technical Brochure

Danfoss AK-PC 551
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
AK-PC 551 Technical brochure RC8CF102 © Danfoss 08-2014 23
Question Solution
How to start and stop
an AK-PC 551 pack
controller?
The AK-PC 551 controller has two options for start/stop of control�
Parameter set via the display:
The parameter “Main switch” is used to start/stop control (see
screen dumps)
Optional start/stop via digital input signal:
The AK-PC 551 controller can also be controlled via a digital input
signal� This function is enabled in the Plant type menu and then
set up in the IO conguration of digital inputs
If any of the two “Main switch signals is in OFF position, the AK-PC
551 will stop all control, set all outputs in standby position and
clear all active alarms�
At the same time the controller will generate a special alarm
“Standby mode alarm in order to indicate that the controller has
been stopped�
How to setup and
connect a pressure
transmitter with 0-20
mA or 4-20 mA current
signals?
Pressure transmitters with current output signals of 0-20 mA
or 4-20 mA MUST be connected to one of the analogue input
terminals AI1, AI2, AI3 or AI4�
The signal type and signal range of the pressure transmitter is
setup in the “IO conguration menu for analogue inputs
In the example the suction pressure signal for suction group A, has
been selected for analogue input 1 and the signal type is selected
as “4-20mA� Please be aware that the minimum and maximum
pressure ranges are set in relative pressure
The power supply for pressure transmitters with current signal
must be connected to the 12 Vdc terminal of AK-PC 551� The signal
wire must be connected to the analogue input pin in question�
How does the wizard
assign functions to
inputs and outputs?
If the AK-PC 551 controller is congured via the wizard, the
required functions are automatically assigned to inputs and
outputs�
At the end of the Setup wizard, the user is asked whether the
controller should apply the settings made in the wizard� Please be
aware that the wizard will overwrite all previous congurations, if
the user selects to apply the wizard settings�
Once the user selects to apply the wizard settings, the required
functions are assigned to inputs and outputs based on simple
priority rules� The rules can be seen in detail in the paragraph
“Example: Check IO conguration

Other manuals for Danfoss AK-PC 551

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-PC 551 and is the answer not in the manual?

Danfoss AK-PC 551 Specifications

General IconGeneral
BrandDanfoss
ModelAK-PC 551
CategoryController
LanguageEnglish

Related product manuals