EasyManua.ls Logo

Danfoss AK-PC 781A - Page 67

Danfoss AK-PC 781A
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AK-PC 781A Capacity controller RS8HE202 © Danfoss 2017-07 67
5. Setup values for tap water cir-
cuits
Press the +-button to go on to the
next page
6. Setup values for heating circuit
5 - Tap water circuits (settings are available only when the
refrigerant selected is CO2, and shall be regulated on a
circuit for tap water).
Control mode: Here the regulation of the circuit can be
started (auto) and stopped (off).
Setpoint: The required temperature for the sensor Stw8
can be set here.
Use ext. ref. offset
A 0-10 V signal must displace the temperaturreference.
Max. Ext. ref. offset
Reference displacement at max. signal (10 V)
Thermostat band: The acceptable temperature variation
around the reference:
Control signal. . Choose between:
Stw8: if regulation shall be done using only this sensor.
S4-S3: (and a Delta T value) if the controller shall regulate
using this temperature difference, until the Stw8 refer-
ence is met. (During S4-S3 regulation, the pump must
always be speed-regulated).
Stw8 + Stw8A: if two temperature sensors are installed in
the hot water receiver.
Stw4: regulation is done using this sensor
Variable speed: Here the pump type is selected. Either
variable speed or on/off.
Advanced settings: The following options are made avail-
able:
Flow switch: Must normally be selected for safety purposes
Kp: Amplification factor
Tn: Integration time
Min. pump speed: Pump speed for start/stop
Max. pump speed: The pump's max. permissible speed
Flowswitch delay: Duration of stable signal before the new
status is used in the regulation.
6 - Heat reclaim circuits (settings are available only when
the refrigerant chosen is CO2, and regulation shall be
done using a circuit for heating).
Control mode: Here the regulation of the circuit can be
started (auto) and stopped (off).
Setpoint: Here the required temperature of sensor Shr8 (or
Shr4) is set.
Use ext. ref. offset
A 0-10 V signal must displace the temperaturreference.
Max. Ext. ref. offset
Reference displacement at max. signal (10 V)
Thermostat band: The permissible temperature variation
around the reference:
Control signal: Choose between:
Shr8: if regulation shall be done using only this sensor.
S4-S3: (and a Delta T value) if the controller shall regulate
using this temperature difference, until the Shr8 refer-
ence has been met.
Shr4: regulation is done using this sensor. (During S4-S3
regulation or Shr4 regulation the pump shall always be
speed-regulated).
Variable speed: Here the pump type is selected. Either
variable speed or on/off.
Heat consumers: (Only when the condensation pressure
shall be increased during heat recovery). The number of
signals that can be received is set here. The signal can be
either 0-10 V or 0-5 V. (Settings under "Advanced" will be
used 0-100% for the signal).
Heat consumer filter
The highest of the received signals are made known over
this period
Additional heat output
The function will reserve a relay. The relay will pull in when
the signal for the heat removers reaches 95%.
Flowswitch delay: Duration of stable signal before the new
status is used in the regulation.
In our example we use the
settings shown
In our example we use the
settings shown
Configuration - continued

Table of Contents

Related product manuals