EasyManua.ls Logo

Danfoss CF-MC - More (2 to 3) CF-MC Master Controllers; CF-RS, -RP, -RD and -RF Room Thermostats; Other System Components; Transmission Test (Link Test)

Danfoss CF-MC
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Guide CF-MC Master Controller
6
01/2016 VIUHK902 Danfoss Heating Solutions
4.9 More (2 to 3) CF-MC Master Controllers
Note! To have a troublefree installation of the CF-MC Master Controller 2 and/or 3, it is recommended to
complete installation of the CF-MC Master Controller 1.
CF-MC Master Controller 1 should be the one connected to the local supply pump.
Up to 3 CF-MC Master Controllers can be connected in one system.
If there are 2 or 3 CF-MC Master Controllers, connect them to a 230 V power supply within a
distance (max. 1.5 m) from CF-MC Master Controller 1, allowing simultaneous handling of all the
CF-MC Master Controllers.
Activate Install mode on CF-MC Master Controller 1 (fig. 20):
Use the menu selection button to select the Install mode. Install LED flashes.
Activate Install mode by pressing OK . Install LED goes ON.
Initiate installation on CF-MC Master Controller 2 or 3 (fig. 20):
Activate installation to CF-MC Master Controller 1 by pressing OK .
Install LED flickers during communication and goes OFF when installation is complete.
Relocate CF-MC Master Controller 2 and/or 3 if necessary. Link test will be initiated automati-
cally on reconnection to 230 V power supply.
If CF-MC Master Controller 2 and/or 3 has it’s own pump, the relays for pump and boiler must
be configured accordingly (see chapter 6.5).
Note! Later removal of CF-MC Master Controller 2 or 3 from CF-MC Master Controller 1 can only be done
by resetting CF-MC Master Controller 1 (see chapter 7.2).
4.10 CF-RS, -RP, -RD and -RF Room Thermostats
Note!
Assignment of Room Thermostats to CF-MC Master Controller should be within a distance of 1.5 m.
Activate Install mode on CF-MC Master Controller (fig. 20):
Use the menu selection button to select the Install mode. Install LED flashes.
Activate Install mode by pressing OK . Install LED goes ON.
Activate Install mode on CF-RD and -RF Room Thermostats (fig. 20/21):
Press the push button . LED and flicker during communication.
Activate Install mode on CF-RS and -RP Room Thermostats (fig. 20/21):
Press the push button / . LED and flicker during communication.
Select output on CF-MC Master Controller (fig. 20/22):
All available output LEDs on CF-MC Master Controller light up, and the first one flashes.
Press output selection button to select desired output (flashes). Accept with OK .
All output LEDs go OFF. Selected output stays ON shortly.
Room Thermostat installation status (fig. 21):
Satisfactory: LED goes OFF.
Not satisfactory: LED flashes 5 times.
Note!
A Room Thermostat can be assigned to several outputs if needed by repeating the installation process.
4.11 Other System Components
The installation procedure of other system components to the CF-MC Master Controller (CF-RC Re-
mote Controller, and CF-RU Repeater Unit) is described in the enclosed instructions for these system
components.
4.12 Transmission Test (Link Test)
The transmission test (link test) between the CF-MC Master Controller and other system components,
is initiated from the other system components like CF-RU Repeater Unit, CF-RC Remote Controller,
etc. See the enclosed instruction for these components for transmission test (link test) procedures.
Room Thermostats
When the transmission test (link test) from a Room Thermostat is received by the CF-MC Master
Controller, the assigned output(s) will flash. This makes it possible to identify the outputs to which a
Room Thermostat has been assigned (fig. 22 - ).

Other manuals for Danfoss CF-MC

Related product manuals