14 VI.72.M4.02 Danfoss 11/97 BC-HM
Row ← (–) Column 0-4 (+) →
0-9
01234
0 P0.0 P0.1 P0.2 P0.3 P0.4
Status Software System Time switch Bus
generation number channel select address
0-15 0,1,2,3,4 0-15
1 P1.0 P1.1 P1.2 P1.3 P1.4
S1 actual S1 reference Total stop Balance Motor
temperature PI circuit 0 or 1 temperature constant
PI circuit -20 til 110 °C 1-899 s
2 P2.0 P2.1 P2.2 P2.3 P2.4
S2 actual S2 reference Temp.diff. Anti-bacteria X
p
- propor-
storage tank/ storage tank/ TS1-TS2 function tional band
room temp. room temp. 1-30 °C 0-99 °C / - - 1-199 K
3 P3.0 P3.1 P3.4
S3 actual S3 frost T
n
- integra-
temperature protection limit tion time
2-10 °C / - - 1-899 s
4 P4.0 P4.1 P4.2 P4.3 P4.4
S4 actual S4 return Return limit Warm-start N
z
-
return max./min. amplification delay time neutral zone
temperature +(20-99) or ±(0-20) 1-899 s 0-9 K
-(20-99)
5 P5.0 P5.3 P5.4
S5 actual S5 Mid-point Tmax.
ext. setpoint ext. pot. PI circuit
0-99 °C -20 to 110 °C
6 P6.0 P6.1 P6.2 P6.3 P6.4
S6 (S2*) actual S6 reference Compensation Compensation Tmin.
temperature storage tank/ base point I/ factor I PI circuit
compensation diff S2-S6 ±(0-20) -20 to 110 °C
temperature ±(0-90)
7 P7.0 P7.1 P7.2 P7.3 P7.4
S1/S2 actual Alarm code Compensation Compensation K
p
- propor-
temperature base point II factor II tional factor
±(0-90) ±(0-20) 0-30
8 P8.0
Normal
temperature
-20 to 110 °C
9 P9.0
Reduced
temperature
-20 to 110 °C
*
See description of position functions, pages 15-21.
Factory settings are shown under the system type concerned, see pages 22-48.
Position overview (matrix)
*