Danfoss EPU 2370 User Manual

Danfoss EPU 2370
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
BC-HM VI.72.M4.02 Danfoss 11/97 25
Factory settings - System types 1-A, 1-B and 1-C
For further information see page 15 to 21.
Row (–) Column 0-4 (+)
0-9
01234
0 P0.0 P0.1 P0.2 P0.3 P0.4
Status Software System type Time switch Slave
generation number channel select adress
F: 1 F: 0.0 F: 15
1 P1.0 P1.1 P1.4
S1 actual hot- S1 reference Motor
water-service hot-water- constant
temperature service temp. F: 17 s
2 P2.3 P2.4
Anti-bacteria X
p
- propor-
function tional band
F: - - (OFF) F: 50 K
3 P3.0 P3.1 P3.4
S3 actual S3 reference T
n
- integra-
temperature frost protection tion time
temperature F: 15 s
F:2 °C
4 P4.0 P4.1 P4.2 P4.4
S4 actual S4 return limit Return limiter N
z
-
return temp. max./min. amplification neutral zone
F: 40 °C F:-4 times F: 3 K
5 P5.0 P5.3
S5 actual S5 scale mid
ext. setpoint point for ext.
setpoint
F: 50 °C
6
7 P7.0 P7.1
S1 actual hot- Alarm code
water-service
temperature
8 P8.0
Normal hot
water-service
temperature Setting in connection with sensors S3 and S4
F: 50 °C and ext. setpoint S5
9 P9.0 F: Factory setting
Reducered hot-
water-service
temperature
F:40 °C