BC-HM VI.72.M4.02 Danfoss 11/97 29
Row ← (–) Column 0-4 (+) →
0-9
01234
0 P0.0 P0.1 P0.2 P0.3 P0.4
Status Software System Time switch Slave
generation number channel select adress
F: 1 F: 0.0 F: 15
1 P1.0 P1.1 P1.2 P1.4
S1 actual S1 reference Valve Motor
charging charging function constant
temperature temperature F: 1 F: 17 s
2 P2.0 P2.1 P2.2 P2.3 P2.4
S2 actual S2 reference S1ref-T.cut-out Anti-bacteria X
p
- propor-
storage tank cut-in F: 5 K function tional band
temperature temperature F: - - (OFF) F: 50 K
3 P3.0 P3.1 P3.4
S3 actual S3 reference T
n
- integra-
temperature frost tion time
temperature F: 15 s
F: 2 °C
4 P4.0 P4.1 P4.2 P4.4
S4 actual S4 return limit Return limit N
z -
- return temp. max./min. amplification neutral zone
F: 40 °C F: -4 times F: 3 K
5 P5.0 P5.3
S5 actual S5 scale mid-
ext. setpoint point for ext.
setpoint
F: 50 °C
6 P6.0 P6.1 P6.2
S6 actual S6 reference Temp. diff.
temperature cut-out T
cut-out
- T
cut-in
temperature F: 5 K
7 P7.0 P7.1
S1 actual hot- Alarm code
water-service
temperature
8 P8.0
Normal hot
water-service
temperature Settings in connection with sensors S3 and S4
F: 50 °C and ext- setpoint S5
9 P9.0 F: Factory setting
Reduced hot
water-service
temperature
F: 40 °C
Factory settings - System types 1-D and 1-E
For further information see page 15 to 21.