Danfoss erc 112 - Menu Functions (Continued); Input Configuration (S1-S4); Digital Input and Output Configuration

Danfoss erc 112
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
"t1A"
Min. -20.0 K
Max. 20.0 K
Default 0.0 K
Air Temperature Adjustment
(applies to non-Danfoss temperature sensors only)
This parameter is a relative value and allows adjustment of the control
sensor temperature.
For instance, at a measured temperature of 7*C and "tAd" set to -2 K,
the input from the control sensor will be 5*C instead.
"t2A"
"t3A"
"t4A"
Inputs and outputs are configurable
There are two steps:
1.
Define the type of sensor attached to the input:
- temperature: light/digital.
2. Define the application for the sensor:
- temperature: control/condenser/evaporator.
- light: ECO/display/both.
- motion
- digital: door sensor.
Please contact your local Danfoss representative for information about
default settings.
NOTE: coded sensors will impact on the number of possible
configurations.
For instance: Danfoss supplies only 2-pole defrost sensors, so input "S3"
will most likely be used as a defrost/evaporator temperature sensor input.
"S1C"
Default Stn
S1 Config/S1C
S2 Config/S2C
S3 Config/S3C
S4 Config/S4C
Available options are:
"Stn": for a standard temperature sensor NTC 5 K @ 25°C and TPE precision.
"Htn": for a high temperature sensor NTC 100 K @ 25°C.
"Pt1": for a temperature sensor Pt1000 ohm @ 0°C (only "S4").
"Ldr": for a light sensor (values given in Luminens).
"dig": for a digital sensor with simple ON/OFF indication
(motion, magnet, switch, buttom).
"S2C"
Default Stn
"S3C"
Default Stn
"S4C"
Default Stn
"S1A"
Default SCo
S1 Application/S1A
S2 Application/S2A
S3 Application/S3A
S4 Application/S4A
Available options are:
"nC": not connected.
"SCo": temperature control.
"EuA": evaporator temperature.
"Con": condenser temperature (Condenser cleaning).
"AuS": only for showing temperature on display.
"Ldr": light sensor, Luminens.
"ECo": external input to control ECO mode.
"doC": door contact, contact closed when door closed.
"doo": door contact, contact open when door closed.
"Pir": motion sensor (only "S3").
"bt5": button 5 (only "S4").
"S2A"
Default nC
"S3A"
Default nC
"S4A"
Default nC
User Guide | ERC 112 Refrigeration Controller
© Danfoss | DCS (vt) | 2019.07 BC200686422115en-000802 | 21