User manual ERC 113 refrigeration controller
"SdS"
Min. no
Max. yes
Default yes
Show Defrost symbol
"no": defrost symbol will not show on display.
"yES": show defrost symbol on display.
"SES"
Min. no
Max. yes
Default yes
Show ECO symbol
"no": ECO symbol will not show on display.
"yES": show ECO symbol on display.
ALA Alarm settings
"HAt"
Min. -100.0°C
Max. 200°C
Default 15.0°C
High Temp Alarm
Absolute value.
By setting "HAt" to the maximum alarms will be deactivated.
"LAt"
Min. -100.0°C
Max. 200°C
Default -50.0°C
Low Temp Alarm
Absolute value.
By setting "LAt" to the minimum value, alarms will be deactivated.
In most situations, the low alarm delay will be set to 0 to warn about
too low a temperature immediately.
"Htd"
Min. 0 min
Max. 240 min
Default 30 min
Alarm delay on high temperature alarm
The number of minutes to wait before sounding an alarm once the
high temperature alarm temperature is reached.
"Ltd"
Min. 0 min
Max. 240 min
Default 0 min
Alarm delay on low temperature alarm
The number of minutes to wait before sounding an alarm once the
low temperature alarm temperature is reached.
"Pdd"
Min. 0 min
Max. 960 min
Default 240 min
Pull down delay
Normally, it is not necessary or desirable to sound an alarm during a pull
down (the initial phase of reaching the desired temperature).
This
parameter prevents the high temperature alarm "HAt" sounding during pull down
and after a defrost for the number of minutes set for the parameter.
NOTE: it does not apply to the low temperature alarm "LAt".
"dod"
Min. 0 min
Max. 60 min
Default 2 min
Door Open delay
It is possible to indicate to customers that a door has accidentally been
left open.
This parameter sets the delay in minutes before the alarm sounds.
This is useful in environments where customers/users may hold the door
open while making their selection. If the door is closed again before
the set number of minutes is reached, the alarm does not sound.
NOTE: a door sensor is required if this parameter is to be activated.
"uAL"
Min. no
Max. yes
Default no
Voltage alarm
"no": no voltage alarm.
"yES": voltage alarm activated.
"LEA"
Min. 0 hour
Max. 96 hour
Default 0 hour
Leakage alarm
Leakage detection for compressor protection.
"0": disable
"Abd"
Min. 0 min
Max. 999 min
Default 0 min
Alarm Buzzer Duration
The alarm sounds for 10 seconds, followed by silence for 50 seconds.
One alarm sequence therefore lasts 60 seconds. These values cannot be
changed. This parameter determines how long in minutes an audible
alarm will continue while there is still a reason to have an alarm.
If set to 999, the alarm will continue to sound until the reason for the
alarm is cleared – for example the temperature has dropped enough or
the door closed. In some cases, it may be necessary for a user or technician
to take action in order to clear the alarm. If set to 0, the alarm will never
sound.
14
DKRCC.ES.RL0.F5.02 Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07