User manual ERC 113 refrigeration controller
"ECt"
Min. 0 min
Max. 180 min
Default 30 min
Action counter time
Door action or "PIR" action within action counter time can trigger
exiting ECO (can only be accessed by Danfoss).
"Edd"
Min. 0 min
Max. 180 min
Default 180 min
Door delay
Door delay after door close to trigger entering ECO
(can only be accessed by Danfoss).
"EPd"
Min. 0 min
Max. 180 min
Default 120 min
Pir delay
"PIR" delay to trigger entering ECO
(can only be accessed by Danfoss).
"SLd"
Min. 0
Max. 80
Default 5
Shop Light Day/SLd
Shop Light Night/SLn
These parameters are set as the percentage of the maximum light and
determine when the device moves into or out of ECO mode for
power-saving purposes.
"SLd" is the amount of ambient light which will cause the device to
move to normal/serving mode from ECO mode
(normally occurs in the morning).
"SLn" is the amount of ambient light which will cause the device to
move to ECO mode from normal/serving mode
(normally occurs in the evening).
"SLn"
Min. 0
Max. 80
Default 3
"tto"
Min. 0 hour
Max. 168 hour
Default 0 hour
Time to pull down
Time which ERC stay in ECO and holiday mode to decide to enter pull
down or serving mode.
"LSd"
Min. 0 min
Max. 180 min
Default 0 min
Light Source delay on ECO
Time delay for light source to change from serving mode source to
ECO mode source.
"Euu"
Min. no
Max. yes
Default yes
EWU active on/OFF
Enable or disable early wake up.
"CLH"
Min. 0 hour
Max. 24 hour
Default 6 hour
Shop close hour
Shop is assumed to be closed when staying in ECO mode longer than
shop close hour.
"ErL"
Min. 0 min
Max. 240 min
Default 120 min
Early wake up time offset
Time of exiting ECO mode for next day=
Time of first activity to exit ECO mode - the early wake-up time.
"0": early wake up function disabled."
"HoL"
Min. 0 hour
Max. 999 hour
Default 72 hour
Holiday Length
In case that no activity has been registered for a number of days,
specified by the holiday, the early-wake-up is deactivated and the
cooler must stay in holiday mode until activity is detected.
ECA ECO management
"Eto"
Min. -25,0 K
Max. 25.0 K
Default 4.0 K
Eco Temperature Offset
This parameter gives a relative temperature in degrees. It is the difference
in temperature for ECO mode operation compared to normal mode.
NOTE: setting a temperature offset may be illegal in some jurisdictions.
"Hto"
Min. -25.0 K
Max. 25.0 K
Default 6.0 K
Holiday Temperature Offset
Increase or decrease of temperature with respect to normal mode
during holiday mode.
16
DKRCC.ES.RL0.F5.02 Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ERC 113C and is the answer not in the manual?

Danfoss ERC 113C Specifications

General IconGeneral
BrandDanfoss
ModelERC 113C
CategoryController
LanguageEnglish

Related product manuals