User manual ERC 113 refrigeration controller
"diE"
Min. 0.0 K
Max. 10.0 K
Default 2.0 K
ECO Differential
Thermostat differential for ECO.
"FoE"
Min. 0 s
Max. 960 s
Default 0 s
ECO Fan on cycle
On time for fan during compressor OFF period in ECO mode.
"FSE"
Min. 0 s
Max. 960 s
Default 0 s
ECO Fan stop cycle
OFF time for fan during compressor OFF period in ECO mode.
"ELC"
Default on
ECO Cabinet light control
"on": always ON (Button is default to control light for all these options).
"oFF": always OFF.
"dor": door sensor only.
"ELd"
Min. 0 min
Max. 10 min
Default 5 min
Eco Light Delay
This parameter causes a delay to the switch from normal to ECO mode
when the shop lights are switched ON or OFF. The ambient light sensor
detects the change in light level and causes a switch mode. With this
parameter set to zero, the switch OFF mode occurs immediately.
If not set to zero (max: 10 minutes), then the change will be delayed by
the number of minutes set.
ASi Assignments settings
"uSA"
Min. no
Max. yes
Default no
MODBUS Safety
"on": MODBUS auto detection is enabled.
"yES": MODBUS communication is deactivaed.
"t1A"
Min. -20.0 K
Max. 20.0 K
Default 0.0 K
Air Temperature Adjustment
(applies to non-Danfoss temperature sensors only)
This parameter is a relative value and allows adjustment of the control
sensor temperature.
For instance, at a measured temperature of 7*C and "tAd" set to -2 K,
the input from the control sensor will be 5*C instead.
"t2A"
"t3A"
"t4A"
Inputs and outputs are configurable
There are two steps:
1.
Define the type of sensor attached to the input:
- temperature: light/digital.
2. Define the application for the sensor:
- temperature: control/condenser/evaporator.
- light: ECO/display/both.
- motion
- digital: door sensor.
Please contact your local Danfoss representative for information about
default settings.
NOTE: coded sensors will impact on the number of possible
configurations.
For instance: Danfoss supplies only 2-pole defrost sensors, so input "S3"
will most likely be used as a defrost/evaporator temperature sensor input.