8-50 Coasting Select
Option: Function:
[3] * Logic OR The eldbus/serial communication port or a
digital input triggers the coasting function.
8-51 Quick Stop Select
Select the trigger for the quick stop function.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals
(digital input) and/or via the eldbus.
NOTICE
When parameter 1-10 Motor Construction is
set to [1] PM non-salient SPM, only
selection [0] Digital input is available.
[0] Digital
input
Activate a start command via a digital input.
[1] Bus Activate a start command via the serial
communication port or eldbus option.
[2] Logic
AND
Activate a start command via the eldbus/serial
communication port and via 1 of the digital
inputs.
[3] * Logic OR Activate a start command via the eldbus/serial
communication port or via 1 of the digital
inputs.
8-53 Start Select
Option: Function:
Select the trigger for the start function.
[0] Digital
input
A digital input triggers the start function.
[1] Bus A serial communication port or the eldbus
triggers the start function.
[2] Logic AND The eldbus/serial communication port and a
digital input trigger the start function.
[3] * Logic OR The eldbus/serial communication port or a
digital input triggers the start function.
8-54 Reversing Select
Option: Function:
Select the trigger for the reversing function.
[0] Digital
input
A digital input triggers the reversing function.
[1] Bus A serial communication port or the eldbus
triggers the reversing function.
8-54 Reversing Select
Option: Function:
[2] Logic AND The eldbus/serial communication port and a
digital input trigger the reversing function.
[3] Logic OR The eldbus/serial communication port or a
digital input triggers the reversing function.
8-55 Set-up Select
Option: Function:
Select the trigger for the set-up selection.
[0] Digital
input
A digital input triggers the set-up selection.
[1] Bus A serial communication port or the eldbus
triggers the set-up selection.
[2] Logic AND The eldbus/serial communication port and a
digital input trigger the set-up selection.
[3] * Logic OR The eldbus/serial communication port or a
digital input triggers the set-up selection.
8-56 Preset Reference Select
Option: Function:
Select the trigger for the preset reference
selection.
[0] Digital
input
A digital input triggers the preset reference
selection.
[1] Bus A serial communication port or the eldbus
triggers the preset reference selection.
[2] Logic AND The eldbus/serial communication port and a
digital input trigger the preset reference
selection.
[3] * Logic OR The eldbus/serial communication port or a
digital input triggers the preset reference
selection.
8-57 Prodrive OFF2 Select
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-58 Prodrive OFF3 Select
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
Parameters EtherNet/IP
24 Danfoss A/S © 06/2016 All rights reserved. MG07H102
55

Questions and Answers: