Parameter Default value 4 set-up
Change during
operation
Conversion
index
Type
Parameter 12-83 SNMP Agent [1] Enabled 2 set-ups TRUE – Uint8
Parameter 12-84 Address Conict
Detection
[1] Enabled 2 set-ups TRUE – Uint8
Parameter 12-89 Transparent Socket
Channel Port
– 1 set-up TRUE 0 Uint16
Parameter 12-90 Cable Diagnostic [0] Disabled 1 set-up TRUE – Uint8
Parameter 12-91 Auto Cross Over [1] Enabled 1 set-up TRUE – Uint8
Parameter 12-92 IGMP Snooping [1] Enabled 1 set-up TRUE – Uint8
Parameter 12-93 Cable Error Length 0 1 set-up TRUE 0 Uint16
Parameter 12-94 Broadcast Storm
Protection
-1% 1 set-up TRUE 0 Int8
Parameter 12-95 Broadcast Storm
Filter
[0] Broadcast only 1 set-up TRUE – Uint8
Parameter 12-96 Port Cong – 1 set-up TRUE – Uint8
Parameter 12-98 Interface Counters 4000 All set-ups TRUE 0 Uint32
Parameter 12-99 Media Counters 0 All set-ups TRUE 0 Uint32
Table 5.3 Parameter List
5.3.3 Conversion
The various attributes of each parameter are shown in
factory setting. Parameter values are transferred as whole
numbers only. Conversion factors are therefore used to
transfer decimals.
A conversion factor of 0.1 means that the value transferred
is multiplied by 0.1. The value 100 is therefore read as 10.0.
Examples:
0 s ⇒ conversion index 0
0.00 s ⇒ conversion index -2
0 ms ⇒ conversion index -3
0.00 ms ⇒ conversion index -5
Conversion index Conversion factor
100 1
75 3600000
74 3600
70 60
67 1/60
6 1000000
5 100000
4 10000
3 1000
2 100
1 10
0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
-6 0.000001
Table 5.4 Conversion Table
Parameters Programming Guide
MG07H102 Danfoss A/S © 06/2016 All rights reserved. 33
5 5