EasyManuals Logo

Danfoss EtherNet/IP Midi Drive FC 280 User Manual

Danfoss EtherNet/IP Midi Drive FC 280
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background image
Attribute Access Name Data type Description
13 Get Fault code Uint
Mapping of parameter 16-90 Alarm Word to CIP-
specic fault codes.
15 Get Control from net Boolean
Parameter 12-31 Net Reference value written from
option.
Table 7.5 Instance Attributes-Class ID 0x29 Control Supervisor Object
CIP malfunction
code
Meaning Frequency converter
code alarm word
CIP malfunction meaning CIP classi-
cation
0 No alarm 0000 0000 No fault
0 Unused 0000 0001 No fault
4210
Frequency converter overtem-
perature
0000 0002
Excessive device temperature
MAR
2240 Ground fault 0000 0004 Short to ground MAU
0 Unused 0000 0008 No fault
8100 Control word timeout 0000 0010 Communication MIR
2310 Overcurrent 0000 0020 Continuous overcurrent MAU
8302 Torque limit 0000 0040 Torque limiting MAR
4310 Motor thermistor 0000 0080 Excess frequency converter temperature MAR
4310 Motor ETR overtemperature 0000 0100 Excess frequency converter temperature MAR
2311 Inverter overloaded 0000 0200 Current inside the device, No. 1 MAR
3220 DC-link undervoltage 0000 0400 Undervoltage inside the device MAR
3210 DC-link overvoltage 0000 0800 Overvoltage inside the device MAR
2130 Short circuiting 0000 1000 Short circuit MAU
2213 Inrush fault 0000 2000 Overcurr.marduring start-up
3130 Mains phase loss 0000 4000 Phase failure MAU
5210 AMT fail 0000 8000 Measurement circuit MIR
1000 Live zero fault 0001 0000 General fault MAR
6100 Internal fault 0002 0000 Internal software fault MAU
7110 Brake resistor power limit 0004 0000 Brake chopper MAU
3300 Motor phase U missing 0008 0000 Output voltage MAU
3300 Motor phase V missing 0010 0000 Output voltage MAU
3300 Motor phase W missing 0020 0000 Output voltage MAU
8100 Fieldbus fault 0040 0000 Communication MIR
5112 24 V supply fault 0080 0000 +24 V power supply MAU
3100 Mains failure 0100 0000 Mains voltage MAR
5110 1.8 V supply fault 0200 0000 Low voltage power supply MAU
7110 Brake resist. short circ. 0400 0000 Brake chopper MAR
7110 Brake chopper fault 0800 0000 Brake chopper MAR
0 Unused 1000 0000 No fault
0 Unused 2000 0000 No fault
0 Unused 4000 0000 No fault
0 Unused 8000 0000 No fault
Table 7.6 Attribute 13 Fault Code
Appendix Programming Guide
MG07H102 Danfoss A/S © 06/2016 All rights reserved. 39
7 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EtherNet/IP Midi Drive FC 280 and is the answer not in the manual?

Danfoss EtherNet/IP Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelEtherNet/IP Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals