Default Value: 0.00
Parameter Type: Range (0.00 — 60000.00)
Parameter Number: 4929
Unit: ms
Data Type: REAL
Access Type: Read/Write
P 9.4.2.6 T3 Live Zero Threshold Value
Description: Set the live zero threshold value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2
Live Zero Response".
Default Value: -10
Parameter Type: Range (-20 — 20)
Parameter Number: 4930
Unit: -
Data Type: REAL
Access Type: Read/Write
P 9.4.2.7 T3 Live Zero Timeout Value
Description: Set the live zero timeout value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2
Live Zero Response".
Default Value: 0.0
Parameter Type: Range (0.0 — 60.0)
Parameter Number: 4931
Unit: s
Data Type: REAL
Access Type: Read/Write
P 9.4.2.8 T3 Temperature Sensor type
Description: Select which type of temperature sensor is connected to the terminal.
Default Value: 0 [No sensor]
Parameter Type: Selection
Parameter Number: 4932
Unit: -
Data Type: UINT
Access Type: Read/Write
The following are the selections for the parameter:
Selection number
Selection name
0
No sensor
1
Pt100
2
2xPt100
3
3xPt100
4
Pt1000
5
Ni1000Tk5000
6
Ni1000Tk6180
7
KTY84-1x0
10
KTY81/82-1x0
11
KTY81/82-121
12
KTY81/82-122
7.6.2.3 Output T4 (Menu Index 9.4.3)
P 9.4.3.1 T4 Terminal Mode
Description: Select the mode for the terminal.
Default Value: 0 [Inactive]
Parameter Type: Selection
Parameter Number: 4045
Unit: -
Data Type: UINT
Access Type: Read/Write
The following are the selections for the parameter
AQ390830267692en-000601 / 136R027356 | Danfoss A/S © 2023.06
General Purpose I/O Installation
and Configuration
Functional Extension Options
Operating Guide