User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use
18 | BC306932151284en-000201
© Danfoss | DCS (ms) | 2020.01
Configuring using the LCD
By pressing the main menu will show up with the options below
Table 02
Main menu navigation
Main Menu Submenu Submenu/status Submenu/status Min Max Default Description Label
Alarms
Active alarms
No alarm
up to 15 alarms
(see table
below)
Up to 15 possible alarms listed by arrow up/down
Reset alarms Reset all actual alarms
Log history View log history
Clear log
history
Clear log history
Login Password *** 200 N/A
Start
Turn On Main swith ON
Turn Off Main swith OFF
Parameters
Unit config
Compressor
0 sec 100 sec 20 sec SDT (Compressor start delay) CM2
5 min
2000
min
45 min PDT (Pull down time) CM3
180 min
2000
min
1440
min
CST (Cycle time) CM4
24 hours
768
hours
160
hours
PLT (Endless purging max time) VA5
Limits settings
0 bar 5 bar 0.5 bar Comp Diff (Hysteresis min allowed ammonia pressure) CM5
0 bar 12 bar 6.5 bar Setpoint (Min allowed ammonia pressure) CM1
Input/Output Input / Output Display & Config

Other manuals for Danfoss IPS 8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss IPS 8 and is the answer not in the manual?

Danfoss IPS 8 Specifications

General IconGeneral
BrandDanfoss
ModelIPS 8
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals