Next go to the Parameters menu for the screen below.
The table below shows all the parameters available to edit along with their definitions.
GEN Parameters > 
General
Function  Default Units
y01 ON/OFF Master Switch (Off/On) On
y05 Temperature Units Select Temperature/Pressure Units (C/F)
Also sets pressure to BAR when C used, PSI 
when F used.
F
y06 Reset Runtime/
Cycle
Reset Runtime/Cycle values (No/Yes), resets to 
No once values are cleared
No
y07 Reset to Default Resets all settings to default values (No/Yes), 
resets to No once values are set to default
No
y08 Night Setback Can be used to put unit into night setback if 
Select Schedule is zero. (Day/Night)
Day
y27 Load Shed Value Current Load Shed value from front end.  (Read 
Only)
--
y28 Load Shed Set If Load Shed Value is above this setting, unit is 
placed in Load Shed Mode (0-4, zero disables 
load shed)
0
y26 Select Schedule If Load Shed Value is above this setting, unit is 
placed in Load Shed Mode (0-4, zero disables 
load shed)
0
y29 Select Title24 Select which schedule in the front end the unit 
will use for night setback.(0-16, zero disables 
using front end schedule)
0
y09 Enable Alarms Master Alarm Enable (No/Yes) Yes
y10 Changeover Delay Set delay time between switching between  
Heat and Cool mode. (0-60)
5 m
y02 Enable Expansion Enable Expansion Module (No/Yes) No
y11 Enable AI Filters Enable AI Filters (No/Yes) Yes
y12 Global AI Filter Set Global AI Filter Value (0, 2, 4, 16)
How many samples are used to average an AI 
sensor.
16
y13 Startup Delay Set power up delay before control starts. (5-600) 600 s
y14 MorningStartup-
Period
Delay between Night Setback and Normal 
Mode(0-360
360 m
y15 Sensors Broadcast Number of sensors to broadcast (Read Only)
y16 Broadcast Sensor 1 Select which sensor to broadcast as sensor 1
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
None
y17 Broadcast Sensor 2 Select which sensor to broadcast as sensor 2
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
None
y18 Broadcast Sensor 3 Select which sensor to broadcast as sensor 3
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
None
y19 Broadcast Sensor 4 Select which sensor to broadcast as sensor 4
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
None
y20 Broadcast Sensor 5 Select which sensor to broadcast as sensor 5
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
None