ALM Parameters >
Alarm Config
Function Default Units
S03 Zone - Low Temp Zone Temp Low Alarm (0.0-40.0) 5.0 °C/°F
S04 Zone - Delay Zone Temp Delay (0-240) 240 m
S05 CO2 - High Level CO2 High Alarm (0-2000) 1000 ppm
S06 CO2 - Delay CO2 Alarm Delay (0-240) 15 m
S07 Fan High Run-
time
Fan High Daily Runtime (0-1500) 1500 m
S08 Fan High Cycle Fan High Daily Cycles (0-1000) 1000
S09 Cool1 High
Runtime
Cool 1 High Daily Runtime (0-1500) 1500 m
S10 Cool1 High Cycle Cool 1 High Daily Cycles (0-1000) 1000
S11 Cool2 High
Runtime
Cool 2 High Daily Runtime (0-1500) 1500
S12 Cool2 High Cycle Cool 2 High Daily Cycles (0-1000) 1000
S13 Cool3 High
Runtime
Cool 3 High Daily Runtime (0-1500) 1500 m
S14 Cool3 High Cycle Cool 3 High Daily Cycles (0-1000) 1000
S15 Cool4 High
Runtime
Cool 4 High Daily Runtime (0-1500) 1500 m
S16 Cool4 High Cycle Cool 4 High Daily Cycles (0-1000) 1000
S17 Heat1 High
Runtime
Heat 1 High Daily Runtime (0-1500) 1500 m
S18 Heat1 High Cycle Heat 1 High Daily Cycles (0-1000) 1000
S19 Heat2 High
Runtime
Heat 2 High Daily Runtime (0-1500) 1500 m
S20 Heat2 High Cycle Heat 2 High Daily Cycles (0-1000) 1000
S21 Heat3 High
Runtime
Heat 3 High Daily Runtime (0-1500) 1500 m
S22 Heat3 High Cycle Heat 3 High Daily Cycles (0-1000) 1000
S23 Heat4 High
Runtime
Heat 4 High Daily Runtime (0-1500) 1500 m
S24 Heat4 High Cycle Heat 4 High Daily Cycles (0-1000) 1000