User Guide | MCX-RTU Rooftop
RS8KE102 | 22
© Danfoss | ADAP-KOOL® | 2018.11
HUM Parameters >
Dehumd
Function Default Units
Dp2 Cp2 Press Target Dehumidification Compr 2 Pressure Target
(0.0-100.0)
8.2 bar/psi
Dp3 Cp3 Press Target Dehumidification Compr 3 Pressure Target
(0.0-100.0)
8.2 bar/psi
Dp4 Cp4 Press Target Dehumidification Compr 4 Pressure Target
(0.0-100.0)
8.2 bar/psi
Gn1 Cp1 PI Gain Dehumidification Compr 1 PI Gain (0.0-
100.0)
10.0
It1 Cp1 Integ Time Dehumidification Compr 1 Integration
Time (5-1000)
120
Gn2 Cp2 PI Gain Dehumidification Compr 2 PI Gain (0.0-
100.0)
10.0
It2 Cp2 PI Integ
Time
Dehumidification Compr 2 Integration
Time (5-1000)
120
Gn3 Cp3 PI Gain Dehumidification Compr 3 PI Gain (0.0-
100.0)
10.0
It3 Cp3 PI Integ
Time
Dehumidification Compr 3 Integration
Time (5-1000)
120
Gn4 Cp4 PI Gain Dehumidification Compr 4 PI Gain (0.0-
100.0)
10.0
It4 Cp4 PI Integ
Time
Dehumidification Compr 4 Integration
Time (5-1000)
120
DMP Parameters >
Damper Config
Function Default Units
DM1 DAM Min Open Damper Min Open (0.0-100.0) 7.0 %
DM2 DAM Max Open Damper Max Open (0.0-100.0) 100.0 %
DM3 DAM Air Target Damper Free Cooling Supply/Mixed Air
Target (0.0-40.0)
18.0 °C/°F
DM4 High Amb Temp
Lockout
Damper Free Cooling High Ambient Lock-
out (0.0-100.0)
25.0 °C/°F
DM5 High Otdr RH
Lockout
Damper Free Cooling High Outdoor RH
Lockout (0.0-100.0)
80.0 %
DM6 High Otdr En-
thalpyLockout
Damper Free Cooling High Enthalpy Lock-
out (0.0-100.0)
60.0
DM7 DM Min Fan
Speed
Damper Min Fan Speed (0.0-100.0) 30.0 %
DM8 DM Max Fan
Speed
Damper Max Fan Speed (0.0-100.0) 75.0 %
DMa Damper PI Gain Damper Free Cooling Pi Gain (0.0-100.0) 5.0
DMi Damper PI Integ
Time
Damper Free Cooling PI Integration Time
(5-1000)
60
Dc1 CO2 Target Damper CO2 Target (0-2000) 900 ppm
Dc2 CO2 Range +/- Damper CO2 Range +/- (0-200) 50 ppm
DM0 Ovrd Value 80.0 %
ALM Parameters >
Alarm Config
Function Default Units
S01 Fan Proof Delay Fan Proof Alarm Delay (0-15) 5 s
S02 Zone - High
Temp
Zone Temp High Alarm (0.0-40.0) 30.0 °C/°F