© Danfoss A/S (RA Marketing/MWA), Nov. 08  RS8FE102, 080R9278    11
OPTYMA
TM
 Control three-phase  Operation and Maintenance Guide
10.
Using  the  holes  made  in  point  9  above,  screw  the 
back  panel to  the  wall  using  4  screws of  a  suitable 
length  for  the  wall  thickness.  Fit  a    rubber  washer 
(supplied)  between  each  screw  and  the  housing 
back panel.
Installing the unit 
(continued)
11.
Now do the electrical wiring as shown below.
Electrical wirings
•  For the electrical wiring please refer to the wiring 
  instruction  and  technical  characteristics  of  the  
  controller being installed.
•  The  controller  power  supply  must  be  on  a  
  dedicated  line,  and  must  be  equipped  with  a  
  suitable device to protect against indirect contacts  
  upstream of the line (differential interrupter).
•  Do  not  route    power  supply  wiring  and  signal  
  wiring  (probes/sensors  and  digital  inputs)  
  in the same raceways or ducts.
•  Do  not  use  multi-polar  cables  which  have  wires 
  connected to inductive/power loads and signalling  
  wires (e.g. probes/sensors and digital inputs).
•  Minimise  the  length  of  connector  wires  so  that  
  wiring  does  not  twist  into  a  spiral  shape,  as  this  
  could  have  a  detrimental  effect  on  the  elec- 
  tronics.
•  If a probe/sensor extension is required, the wires  
  must have a diameter of at least 1 mm
2
.
•  All wiring must  be of a diameter suitable  for the  
  relevant  power  levels.  The  degree  of  insulation  
  must  be  compatible  with  the  applied  voltages.  
  Preferably  use  cables  with  flame-retardant  
  insulation  and  a  low  smoke  emission  where  fire  
  regulations apply.
•  It is essential to connect the clamp marked PE 
  to the earth of the supply system.
  If necessary, please check the eectiveness of  
  the earthing system.
•  Do  not  connect  to  the  PE  clamp  conductors  
  any dierent than the external protection.