24  RS8FE102, 080R9278   © Danfoss A/S (RA Marketing/MWA), Nov. 08
OPTYMA
TM
 Control three-phase  Operation and Maintenance Guide
In the event of any anomalies, the OPTYMA
TM
 Control 
warns  the  operator  by  displaying  alarm  codes  and 
sounding  the  warning  buzzer  inside  the  control 
Alarm codes
panel. If an alarm is tripped, the display will show one 
of the following messages:
Alarm code Possible cause Solution
E0 Cold room temperature sensor not working 
properly
•  Check that the cold room temperature    
  sensor is working properly.
•  If the problem persists, replace the sensor.
E1 Defrost sensor not working properly
(In this case defrosts will last time d3)
•  Check that the defrost sensor is working    
  properly.
•  If the problem persists, replace the sensor.
E2 Eeprom alarm
An EEPROM memory alarm has been detected
(All outputs except the alarm are deactivated)
•  Switch unit o and back on again.
E8 Man-in-cold-room alarm •  Reset the alarm input inside the cold room
Ec Compressor protection tripped (e.g. thermal 
protection or max. pressure switch)
(All outputs except the alarm– where 
applicable – are deactivated)
•  Check that compressor is working properly.
•  Check compressor absorption.
•  If the problem persists, contact the    
  technical assistance service.
Temperature 
shown on 
display is 
flashing 
Minimum or maximum temperature alarm.
The temperature inside the cold room has 
exceeded the min. or max. temperature 
alarm setting (see variables A1 and A2, user 
programming level)
•  Check that the compressor is working    
  properly.
•  Sensor not reading temperature correctly or 
  compressor start/stop control not working.